content loaded

Overview:

IC/SP interchangeable cartridge style thermostatic scald protection valve protects facility personnel from excessively hot temperatures being released from safety showers, facewash, and eyewash stations. The IC/SP valve should be installed within the heated system and is purely water temperature sensing. The valve will initiate flow when the thermostatic actuator senses water temperature above the valve's set-point (typically 98°F [36.7°C]) and will remain open as long as the discharge water temperature is within 10˚F of the open set-point (typically above 95°F [35°C]). The thermal actuator is always wetted, making this valve preferable for heat traced lines where scald protection flow is not required unless heat tracing fails.

Features:

  • Protects safety showers from over-temperature conditions, keeping personnel safe
  • Designed to be Tee'd into larger diameter pipe lines
  • Self-operating, no power or signal required
  • Exclusive Thermoloid® thermal actuator
  • Brass or stainless steel body, fittings, and plugs
  • IC/SP temperatures up to 105°F meet ANSI Z358.1 standards
Quote

"Our mission is to be regarded by our customers and our community as the best supplier of automation and control product solutions to industry."

Michael R Gallagher

Centro President

QTY:

3/4IC/SP-115
Image may not be the actual product. Please refer to the full technical specs and MPN for exact details.
3/4IC/SP-115

MPN: 195-000000-115

Part # 195-000000-115

$242.18
$250.00 You save 3%